There is a useful mathematical distinction between a percentage increase in a rating and a percentage reduction in energy for the same cooling amount. In a simplified example, increasing a rating from 16 to 20 is a 25% increase: (20 − 16) ÷ 16.
Using those ratings as simplified seasonal conversion factors, an assumed eight million Btu of cooling corresponds to 500 kWh at 16 Btu per watt-hour: 8,000,000 ÷ 16 ÷ 1,000. At 20, the same arithmetic gives 400 kWh. The reduction is 100 kWh, or 20% of the original 500 kWh—not 25%.
This calculation teaches the inverse relationship. It is not a prediction of actual building use, and it does not compare peak demand or heating. Real seasonal performance and cost need an appropriate model or measurements, with the relevant assumptions visible.
The same care applies to cost: the energy-rate assumption, fixed charges, and other loads affect what a customer pays. Do not turn the simplified 20% cooling-energy example into a 20% reduction in the entire electricity bill.